W-10KL 10 kVA laagfrequente online UPS met isolatie transformator, 3-fase 380 V input/output
| Capcity: | 10KVA/8KW | Input: | 3 x 380VAC/400VAC (3Ph + N) |
| Frequency: | 50Hz&60Hz | Nominal Battery Voltage: | 384 VDC (Based on 32pcs batteries) |
| Precision: | Stationary: ±1% Transitory: ±5% (load variations 100-0-100%) | Waveform: | Pure Sinewave |
| Output: | 3 x 380VAC/400VAC (3Ph + N) | Transfer Time: | Zero |
| Current Limit: | High overload, short-circuit: RMS Voltage Limit High Crest-Factor current: Peak Voltage Limit | Charging Current: | Default 10A; Maximum 40A; 5A@ full load |
| Capacity: | 10 kVA / 8 kW | Topology: | Low frequency, online double-conversion |
| Input / Output: | 380 / 400 / 415 V AC, 3-phase | Input Voltage Range: | 285–485 V AC (Ph-Ph) |
| Input frequency range: | 50 / 60 Hz, ±10% | Isolation transformer: | Built-in output isolation transformer |
| Transfer Time: | 0 ms (mains to battery) | Battery system: | 384 VDC nominal, 32 × 12 V batteries (29–32 adjustable) |
| High Light: | 10KVA/8KW UPS met lage frequentie,Zuivere Sinewave-Noodvoeding,Nul overdrachtstijd UPS met dubbele ingang |
||
De W-10KL biedt tot 8 kW aan beveiligde output voor driefasige schakelpanelen, elektrische testbanken en industriële hulpapparatuur. Het online dubbele conversie ontwerp omvat een ingebouwde output isolatietransformator en 0 ms net-naar-batterij overschakeling. Aparte hoofd- en bypass-ingangen en een externe 384 VDC batterijbank maken het mogelijk het back-upsysteem te configureren voor de locatie.
Een compacte driefasige belasting matchen
De 8 kW outputlimiet is net zo belangrijk als de 10 kVA nominale waarde. Maak een lijst van de daadwerkelijke besturingsapparatuur, hulpmotoren en testinstrumenten voordat u beslist welke circuits onder back-up stroom moeten blijven.
Het ingangsspanningsbereik van de gelijkrichter is 285-485 V AC lijn-naar-lijn; de bypass heeft zijn eigen smallere venster van 304-456 V AC. Dit zijn verschillende operationele paden en moeten afzonderlijk worden beschouwd bij het beoordelen van de spanningsgegevens van de locatie.
Waar de W-10KL past
Dimensioner deze unit niet op basis van het typeplaatje van een complete machine als alleen het besturingsgedeelte back-up nodig heeft. Scheid essentiële circuits van motoren of verwarmingselementen die niet onder stroom hoeven te blijven.
Batterijconfiguratie
De W-10KL gebruikt een externe VRLA batterijbank. Het nominale systeem is 384 VDC met 32 x 12 V batterijen. Het aantal batterijen kan worden geconfigureerd van 29 tot 32 batterijen, wat overeenkomt met 348 / 360 / 372 / 384 VDC.
Laadspanning is instelbaar van 395-435 VDC. De fabrikant vermeldt laadstroomwaarden tot 40 A en 5 A bij volledige UPS-belasting. Beschikbare laadstroom is afhankelijk van de UPS-belasting en de geleverde laderconfiguratie. De Ah-capaciteit van de batterij moet worden geselecteerd op basis van de aangesloten belasting en de vereiste back-uptijd.
Technische specificaties
Bekijk volledige technische specificaties
Hoofdingang
| Nominale ingangsspanning | 380 / 400 / 415 V AC |
|---|---|
| Ingangsspanningsbereik | 165-280 V AC (Ph-N); 285-485 V AC (Ph-Ph) |
| Fase | 3Ph + N + PE |
| Ingangsfrequentie | 50 / 60 Hz, ±10% |
| Ingang vermogensfactor | ≥0,7 zonder filter; ≥0,97 met filter |
| Gelijkrichtertechnologie | SCR |
| Input THDi | <50% zonder filter; <15% met filter |
Statische bypass ingang
| Bypass spanningsbereik | 176-264 V AC (Ph-N); 304-456 V AC (Ph-Ph) |
|---|---|
| Fase | 3Ph + N + PE |
| Frequentie tracking bereik | 50 / 60 Hz, ±10% |
| Generator ingang | Ondersteund |
| Bypass overbelastingscapaciteit | 150-180%: 1 uur tot 300 seconden; >180%: 300 seconden |
Output
| Nominale capaciteit | 10 kVA / 8 kW |
|---|---|
| Nominale outputspanning | 380 / 400 / 415 V AC, 3Ph + N |
| Output spanningsregeling | ±1% |
| Output vermogensfactor | 0,8 |
| Output frequentie – lijnmodus | (50 / 60) ±0,01 Hz |
| Output frequentie – batterijmodus | (50 / 60) ±0,01 Hz |
| Output golfvorm | Sinusgolf |
| THDv – resistieve belasting | ≤2% |
| THDv – niet-lineaire belasting | ≤4% |
| Utility-naar-batterij overschakeltijd | 0 ms |
| Efficiëntie – lijnmodus | 89% |
| Efficiëntie – batterijmodus | 90% |
Inverter overbelasting
| ≤110% | 60 minuten |
|---|---|
| ≤125% | 10 minuten |
| ≤150% | 1 minuut |
| >150% | 200 ms |
Gelijkrichter, batterij en lader
| Gelijkrichter type | 6-puls |
|---|---|
| Nominale DC spanning | 384 VDC |
| Laadspanning | 395-435 VDC, instelbaar |
| Batterijtype | VRLA verzegelde loodzuur batterij |
| Aantal batterijen | 32 stuks nominaal; 29-32 configureerbaar |
| Batterijstring spanning | 348 / 360 / 372 / 384 VDC |
| Laadstroom | Tot 40 A; 5 A bij volledige UPS-belasting (door de fabrikant vermelde waarden; beschikbare stroom is afhankelijk van de operationele belasting en de laderconfiguratie). |
Communicatie en beheer
| Communicatie | RS232, USB, RS485, droge contacten; 1 communicatiekaartslot voor optionele SNMP-kaart |
|---|---|
| Display | 3,5-inch LCD; optioneel 7-inch kleurenaanraakscherm |
| Alarmfuncties | Output overbelasting, utility-afwijking, UPS-fout, laag batterijvoltage, alarmgeschiedenis |
| Bescherming | Output kortsluiting, output overbelasting, overtemperatuur, laag batterijvoltage, output over/onder voltage, ventilatorfout, overspanningsbeveiliging |
| ECO-modus | Ondersteund |
| EPO | Ondersteund |
| Power walk-in | Ondersteund* |
| Synchronisatiecontroller | Optioneel* |
| UPS classificatie | VFI-SS-111 |
| Parallelle eenheden | 4 stuks |
Omgevings- en fysieke gegevens
| Bedrijfstemperatuur | 0-55°C |
|---|---|
| Opslagtemperatuur | -25-55°C, exclusief batterijen |
| Relatieve vochtigheid | <95%, niet-condenserend |
| Bedrijfshoogte | 0-1500 m bij 100% belasting |
| Geluidsniveau | 70 dB bij 100% belasting |
| Beschermingsgraad | IP20 |
| Conformele coating | Ondersteund |
| Stoffilter | Ondersteund |
| Afmetingen | 405 × 656 × 817 mm (B × D × H) |
| Gewicht | 118 kg |
Normen waarnaar wordt verwezen in de specificaties van de fabrikant
| UPS EMC-vereisten | IEC/EN 62040-2 |
|---|---|
| EMC immuniteitstestmethoden | IEC 61000-4-2; IEC 61000-4-3; IEC 61000-4-4; IEC 61000-4-5; IEC 61000-4-6; IEC 61000-4-8 |
| UPS prestaties | IEC 62040-3 |
| Referenties voor de Chinese markt | GB/T 14715-2017; YD/T 1095-2018 |
Deze referenties verschijnen in de specificaties van de fabrikant en zijn op zichzelf geen bewijs van conformiteit met een specifieke normeditie. Vraag indien nodig de relevante testrapporten of verklaringen aan.
*Functies gemarkeerd met een asterisk zijn configureerbare opties volgens de bron specificatie. Specificaties kunnen worden gewijzigd.
Installatie overwegingen
Controleer fasevolgorde, neutrale en beschermende aardverbindingen aan de hand van de elektrische schema's. Identificeer welke downstream circuits daadwerkelijk zijn opgenomen in de 8 kW back-up belasting voordat u de AC-onderbrekers en kabelroute kiest.
De batterijbank is extern. Reserveer er een aparte locatie voor, bereken de ontlaadstroom voor de vereiste back-up periode, en houd DC-beveiliging toegankelijk voor onderhoud.
Vraag een W-10KL offerte aan
Voor een configuratiebeoordeling, geef uw aangesloten belasting in kW of kVA, site input/output spanning, vereiste back-up tijd, en eventuele motorstart- of generatorvereisten. Wij kunnen de UPS en externe batterijregeling aan de hand van die details beoordelen.
Offerte aanvragenNog een UPS capaciteit nodig?
Bekijk de complete Low Frequency UPS serie voor andere driefasige capaciteiten en configuraties.